Skip to main content

Delivery of fuels

Info on acceptance

Waste acceptance

The acceptance of substitute fuels is only possible on the basis of a valid waste management contract with Hamburger Rieger GmbH, business unit power station and requires a valid approval under waste management legislation. There can be no unloading of vehicles without prior notification. Vehicle street unloading with prior notification for pickups and flat-bed trucks via walking floor, large tipper and container vehicles (unloading via rear end).

Acceptance hours

Mondays to Fridays from 6:00 to 21:00
Saturdays by arrangement

Positive catalouge

Substitute fuels provided for

The waste listed in the PDF (substitute fuels) is permitted for acceptance and treatment in the facility:

The waste received also keep the limitations of the "thresholds for pollutant content of the original substance" - Annex IV, Table 1 of the Notes to the enforcement allocation of waste to the waste types a mirror entry - Brandenburg - of 12 February 2007 (OJ No. 9 from 07/04/2007 S.467) a.


Date of issue: 2014-04-10

Acceptance conditions of the EBS heating plant

For acceptance and treatment in the facility, the substitute fuel must fulfil the following requirements:

Bulk

  • Granulation: 0-800mm
  • Bulk density: von 150kg/m³ bis 800kg/m³
  • Consistency: solid; free liquid not permitted

Transportable baled goods

  • Edge length: max. 800mm
  • Edge length (a+b+c): ≤ 1.500 mm
  • Excess lengths: not permitted
  • Small particles: ≤ 10Ma%

 

Ceramics, sand, porcelain, glass, FE and NE metals     Total ≤ 10 Ma%

 Unit         50% percentile     100% percentile
Calorific value Hu     kJ/kg13.00018.000
Water contentMa-%3035
Ash contentMa-%2530
Analytics
ChlorineMa-%1.21.5
SulphurMa-%0.60.8
FluorineMa-%0.070.1
 Median value    
mg/kg
80. Percentile value
(mg/kg dry matter)
PCB Polychlorinated biphenyls      < 10
PCP Pentachlorphenol < 5
Heavy metals  
As Arsenic513
Cd Cadmium49
Co Cobalt612
Cr Chrome125250
Cu Copper350-
Hg Mercury0.61.2
Mg Manganese250500
Ni Niobium80160
Pb Lead190-
Sb Antimony2560
Sn Tin3070
Tl Thallium12
V Vanadium1025
  • Fireworks, explosive, ammunition, radioactive substances, pressurised gas cylinders
  • Medicines, paints, solvents
  • Vehicle tyres, car parts, white goods
  • Stones, earth, construction waste, compact metal parts

The substitute fuels must not contain any hazardous waste (in particular hazardous waste in the sense of the AVV).

The accepted waste also complies with the restrictions imposed by the “Threshold values for damaging contents in the original substance” – Appendix IV table 1 of the Vollzugshinweise zur Zuordnung von Abfällen zu den Abfallarten eines Spiegeleintrages (Implementation notes on the classification of waste into types of waste of a mirror entry – Brandenburg – of 12 February 2007 (ABl. No. 9 of 07.04.2007 p.476).